What an F-Gas record must include for catering refrigeration
The records GB F-Gas rules ask for on fridges, freezers, cold rooms and ice machines, who has to keep them, for how long, and how to fill them in on site without slowing the job down.
BLBarnabas Looney4 min read
If you service commercial refrigeration in Great Britain, the F-Gas record is the one piece of paperwork an inspector, a customer's auditor or a facilities manager is most likely to ask for. It is also the one most often filled in badly: a charge figure with no refrigerant type, a leak check with no result, or a top-up with no note of where the gas came from.
This guide sets out what the record has to contain, who is responsible for keeping it, and a simple way to make sure every visit produces a complete one.
Which equipment needs an F-Gas record
The record-keeping duty applies to stationary refrigeration, air conditioning and heat pump equipment that contains fluorinated gas equivalent to 5 tonnes of CO₂ or more. In a commercial kitchen that typically means:
- walk-in cold rooms and freezer rooms with remote condensing units
- larger blast chillers and multideck display chillers
- some ice machines and back-bar coolers, depending on the gas and charge
- split air conditioning in the kitchen or front of house
Small integral cabinets running R290 (propane) or R600a are usually well below the threshold, because hydrocarbons have a global warming potential (GWP) of around 3. A 6 kg R404A cold room, on the other hand, is about 23.5 tonnes CO₂e and is firmly in scope. If you're not sure, work out the CO₂ equivalent first. We cover how in How to calculate CO₂ equivalent for a fridge or cold room.
What the record has to show
Government guidance for GB says operators must keep, for at least five years:
- The quantity and type of F-gas in the equipment when it was installed.
- Any gas added during installation, maintenance or servicing, or because of a leak, with the type and amount.
- The dates and results of every mandatory leak check.
- Gas recovered, and whether it was recycled or reclaimed. If it went to a reclaim or destruction facility, the record needs that facility's name, address and certificate number.
- Who did the work: the name, address and F-Gas company certificate number of the business that installed, serviced, repaired or decommissioned the equipment.
- What happened at end of life: how the gas was recovered and disposed of when the system was decommissioned.
In practice, a good engineer's record for a single visit looks like this:
| Field | Example |
|---|---|
| Equipment | Walk-in cold room, Foster condensing unit, serial F12345 |
| Refrigerant | R404A |
| Charge | 6.0 kg |
| CO₂ equivalent | 23.53 tonnes |
| Hermetically sealed | No |
| Automatic leak detection fitted | No |
| Work done | Leak check |
| Method | Direct, electronic leak detector, serial LD-9981 |
| Result | Pass |
| Gas added / recovered | None |
| Engineer F-Gas certificate | FG-123456 |
| Company F-Gas certificate | REFCOM 12345 |
| Next leak check due | 12 months |
Who keeps the record: you or the customer?
Legally the duty sits with the operator, which is usually the business that owns or controls the equipment (the restaurant, hotel or school). In reality almost every operator relies on the service company to produce the record and leave them a copy. If your report is incomplete, it's your customer who is exposed, and it's your name on the paperwork.
Treat it as part of the service: leave the customer a signed copy on the day, and keep your own copy against the equipment so you can see its history next time.
The mistakes that cause problems
No refrigerant type. A charge of "6 kg" on its own means nothing. The CO₂ equivalent and the leak check interval both depend on the gas.
Recording a top-up without a leak check. If you add gas, there's a reason. Record the leak check, where the leak was, and the repair.
Forgetting the follow-up check. After a leak is repaired, the system must be checked again within one month to confirm the repair worked. Put the date on the record before you leave.
Missing certificate numbers. Both the engineer's personal F-Gas certificate and the company certificate (REFCOM, Quidos, BESCA or similar) should appear.
Recovered gas with no destination. If you recover gas, record the cylinder number and where it's going: reused on site (recycled), sent for reclaim, or sent for destruction. Waste carrier and consignment note details belong here too.
Northern Ireland, the Isle of Man and Ireland
Northern Ireland follows the EU F-Gas Regulation rather than the GB version, and the EU rules were revised in 2024. The Isle of Man, the Channel Islands and the Republic of Ireland each have their own arrangements. The record above covers the core information everywhere, but check the local rules if you work across borders.
Making it quick on site
The record only gets filled in properly if it takes less effort than skipping it. Three things help:
- Pre-fill from the equipment record. Refrigerant, charge and CO₂e shouldn't be typed on every visit. They belong to the equipment.
- Remember the engineer's details. Certificate numbers and leak detector serials don't change from job to job.
- Make the important fields required. If the job can't be completed without a leak check result and the next due date, it won't be.
CaterTrackr's F-Gas sheet works this way: it fills in the gas, charge and CO₂e from the equipment, works out the next leak check date from the CO₂e (doubling it when automatic leak detection is fitted), and sets the one-month follow-up when you record a repaired leak.
This guide is a practical summary, not legal advice. The GB F-Gas Regulation and the government's guidance on recording F-gas are the definitive sources.