F-Gas leak check intervals explained: 5, 50 and 500 tonnes CO₂e

How often commercial fridges, freezers and cold rooms must be leak checked under GB F-Gas rules, how automatic leak detection and hermetic sealing change that, and what to do when you find a leak.

BLBarnabas Looney3 min read

Leak check frequency under the F-Gas rules isn't set by the size of the system in kilograms. It's set by the CO₂ equivalent of the refrigerant charge: the charge in kilograms multiplied by the gas's global warming potential (GWP), divided by 1,000 to give tonnes.

That's why two identical-looking cold rooms can have completely different obligations: one running R404A (GWP 3,922) and one running R449A (GWP 1,397).

The GB intervals

CO₂ equivalent of the charge Maximum interval between leak checks With automatic leak detection fitted
Under 5 tonnes No mandatory check No mandatory check
5 to under 50 tonnes 12 months 24 months
50 to under 500 tonnes 6 months 12 months
500 tonnes or more 3 months 6 months (leak detection is mandatory at this size)

Hermetically sealed systems that are labelled as such don't need periodic checks unless they contain 10 tonnes CO₂e or more. Most plug-in cabinets are hermetically sealed; split systems and cold rooms with site-made pipework are not.

What that means in kilograms

Government guidance gives some handy equivalents for common gases. For R404A, the 5-tonne threshold is about 1.3 kg, 50 tonnes is about 13 kg, and 500 tonnes is about 127 kg. For R134a, the same thresholds are roughly 3.5 kg, 35 kg and 350 kg.

A few typical kitchen examples:

Equipment Gas and charge CO₂e Interval
Walk-in cold room R404A, 6 kg 23.5 t 12 months
Freezer room R404A, 14 kg 54.9 t 6 months
Remote multideck R449A, 9 kg 12.6 t 12 months
Integral bottle cooler R290, 0.15 kg ~0 t None
Back-bar cooler R134a, 0.4 kg (sealed) 0.57 t None

What counts as a leak check

A leak check is a proper examination by a certified person, not a glance at the sight glass. The usual methods are:

  • Direct: an electronic leak detector (record its serial number), bubble solution or UV dye, working round joints, valves, seals and vibration points.
  • Indirect: analysing system parameters such as pressures, temperatures, compressor current and liquid levels for signs of gas loss, usually followed by a direct check where something looks wrong.

Write down the method used, the result, and the date. A check without a recorded result doesn't count for much if you're ever asked to prove it.

When you find a leak

If you find a leak, three things follow:

  1. Repair it without undue delay. Don't just top up and leave.
  2. Record it: where the leak was, what you did, and how much gas went back in.
  3. Re-check within one month to confirm the repair holds. Book the follow-up before you leave site and put the date on the record.

If the repair needs parts you don't have on the van, that's a return visit. Make sure it gets booked and the parts get ordered, rather than relying on a note on a paper sheet.

Common traps

Using the wrong GWP. GB F-Gas calculations use the GWP values from the IPCC's Fourth Assessment Report (AR4). R404A is 3,922 on that basis; you'll see other figures quoted from later reports.

Assuming small means exempt. Under 2 kg of R404A can still be over 5 tonnes CO₂e.

Forgetting systems were converted. A retrofit from R404A to R449A or R452A changes the CO₂e and possibly the interval. Update the equipment record when the gas changes.

Letting the date drift. "Annual" means within 12 months of the last check, not "sometime next year".

Setting the next date automatically

The easiest way to stay compliant is to work out the next leak check from the CO₂e at the time you do the check. CaterTrackr's F-Gas sheet does this for you: it calculates the CO₂e from the equipment's gas and charge, sets the next check at 3, 6 or 12 months, doubles it if automatic leak detection is fitted, and leaves it blank for systems that don't need one.

A practical summary of the GB rules for catering refrigeration. Northern Ireland follows the revised EU F-Gas Regulation. Always check the current guidance on gov.uk.