How to calculate CO₂ equivalent for a fridge or cold room
A worked guide to CO₂e for commercial refrigeration, with GWP values for the gases you'll find in UK kitchens and examples for R404A, R449A, R134a and R290.
BLBarnabas Looney3 min read
CO₂ equivalent (CO₂e) is the number that decides whether a system needs F-Gas leak checks, how often, and whether the 2020 servicing ban on high-GWP virgin gas applies to it. It's simple to work out once you have two facts from the data plate.
The formula
CO₂e (tonnes) = charge (kg) × GWP ÷ 1,000
- Charge is the total refrigerant in the system in kilograms. Take it from the data plate, plus any additional charge added on site and recorded at installation.
- GWP is the global warming potential of that refrigerant. GB F-Gas rules use the IPCC Fourth Assessment Report (AR4) values.
GWP values for common kitchen refrigerants
| Refrigerant | Type | GWP (AR4) |
|---|---|---|
| R404A | HFC blend | 3,922 |
| R507A | HFC blend | 3,985 |
| R452A | HFC/HFO blend | 2,140 |
| R410A | HFC blend | 2,088 |
| R407F | HFC blend | 1,825 |
| R407C | HFC blend | 1,774 |
| R134a | HFC | 1,430 |
| R449A | HFC/HFO blend | 1,397 |
| R448A | HFC/HFO blend | 1,387 |
| R32 | HFC | 675 |
| R1234yf | HFO | 4 |
| R290 (propane) | Hydrocarbon | 3 |
| R600a (isobutane) | Hydrocarbon | 3 |
| R744 (CO₂) | Natural | 1 |
Worked examples
Walk-in cold room, 6 kg of R404A 6 × 3,922 ÷ 1,000 = 23.53 tonnes CO₂e. That's between 5 and 50 tonnes, so the leak check interval is 12 months.
Freezer room, 14 kg of R404A 14 × 3,922 ÷ 1,000 = 54.91 tonnes. Over 50 tonnes means 6-monthly checks. It's also over 40 tonnes, so the GB servicing ban means you can't top it up with virgin R404A. Reclaimed or recycled gas is allowed until 2030.
Same freezer room retrofitted to R449A 14 × 1,397 ÷ 1,000 = 19.56 tonnes. The retrofit drops it to 12-monthly checks and takes it out of the servicing ban.
Upright cabinet, 0.4 kg R134a, hermetically sealed 0.4 × 1,430 ÷ 1,000 = 0.57 tonnes. No mandatory leak checks.
Bottle cooler, 0.15 kg R290 0.15 × 3 ÷ 1,000 = 0.0005 tonnes. Hydrocarbons are not fluorinated gases, so F-Gas leak checks don't apply, although you still need the right training to work safely with flammable refrigerants.
Useful thresholds to remember
| Threshold | Why it matters | R404A equivalent |
|---|---|---|
| 5 t | Leak checks and records start | about 1.3 kg |
| 10 t | Hermetically sealed systems start needing checks | about 2.6 kg |
| 40 t | Servicing ban on virgin gas with GWP of 2,500 or more | about 10.2 kg |
| 50 t | Checks go to 6-monthly | about 13 kg |
| 500 t | 3-monthly checks, automatic leak detection mandatory | about 127 kg |
Rounding and recording
Record CO₂e to two decimal places on the F-Gas record, alongside the gas type and charge it came from. Don't round down to slip under a threshold. If the charge isn't known exactly, use the data plate figure plus any additional charge recorded at commissioning.
When the gas changes after a retrofit, update the equipment record straight away. Otherwise every future visit will carry the wrong figure.
Let the app do it
In CaterTrackr the refrigerant and charge are stored against the equipment, so the F-Gas sheet arrives with the CO₂e already worked out, and the next leak check date set from it. If the engineer corrects the charge on site, the CO₂e and the due date update with it.
GWP values are AR4 figures as used for GB F-Gas calculations. Northern Ireland follows the revised EU F-Gas Regulation.
Do your job sheets, F-Gas records and return visits on your phone.
CaterTrackr is job management for catering engineers. 30 days free, no card needed, £35 a person a month after.
Barnabas Looney
Barnabas Looney writes the CaterTrackr blog: practical guides on F-Gas, gas safety, servicing and running a catering equipment firm in the UK.