Kitchen extraction and TR19: what catering engineers should check and record

Where catering engineers fit into kitchen extraction maintenance, how TR19 Grease cleaning frequencies work, and the canopy, fan and interlock checks to do on every visit.

BLBarnabas Looney2 min read

Grease in kitchen extract ductwork is a well-known cause of commercial kitchen fires, and insurers increasingly ask for proof that extraction is cleaned and maintained. Specialist duct cleaners do the deep cleans, but catering engineers are on site far more often, and are well placed to spot problems early.

What TR19 is

TR19 Grease, published by BESA, is the specification most UK insurers and facilities managers refer to for cleaning grease extract systems. It sets out how systems should be cleaned and verified, and how often.

A common rule of thumb from TR19 links cleaning frequency to how much the kitchen is used each day:

Daily use Typical cleaning interval
Heavy (12 to 16 hours) Every 3 months
Moderate (6 to 12 hours) Every 6 months
Light (2 to 6 hours) Every 12 months

Measured grease thickness can bring cleaning forward. Always check the current edition and the customer's insurance terms.

What a catering engineer should check

Canopy

  • grease filters fitted, the right type (baffle filters are usual), and undamaged
  • filter condition: clean, needs cleaning, or needs replacing
  • grease gutters and drip trays not overflowing
  • canopy lighting working
  • access panels in place and sealed

Visible grease

Note any visible build-up in the duct beyond the filters and grade it as light, moderate or heavy. Heavy deposits mean the customer needs a deep clean, and you should tell them so in writing.

Fan and controls

  • extract fan running, no unusual noise or vibration
  • supply or make-up air fan, where fitted
  • belts, bearings and anti-vibration mounts
  • speed controller

Interlock

  • the gas solenoid closes when the extract fan stops
  • airflow or pressure proving switch working
  • manual reset needed after a shutdown
  • emergency stop buttons

See Gas interlocks in commercial kitchens for more.

Record the last and next deep clean

Ask the customer for their last TR19 clean certificate and record the date. Recommend the next date based on usage. It's a simple advisory that customers often haven't thought about, and their insurer will.

On CaterTrackr

The extraction canopy sheet covers filters, grease build-up, the fan side and the interlock, and records the last TR19 deep clean and when the next one is due. Put the canopy on a plan alongside the cooking equipment, so it's checked at every service visit.