Commercial catering gas safety checks: what goes on the record (CP42-style)
A step-by-step guide to the annual gas safety inspection in a commercial kitchen, covering tightness testing, ventilation, interlocks, CO₂ levels, appliance checks and the record you leave with the customer.
BLBarnabas Looney4 min read
Every commercial kitchen with gas appliances needs them maintained in a safe condition, and in practice that means an annual gas safety inspection by a Gas Safe registered engineer qualified for commercial catering. The record left behind is often called a "CP42", after a widely used form for catering establishments.
There's no single mandatory form. What matters is that the inspection covers the installation, the ventilation and every appliance, and that the record shows what was found and what action was taken.
Before you start
- Check your own registration and qualifications cover the work: core commercial catering (CCCN1) plus the relevant COMCAT appliance categories.
- Walk the kitchen with the person in charge. Find the emergency isolation valve, the interlock panel, the CO₂ monitor if fitted, and every gas appliance, including the ones tucked under a counter.
- Note the gas type (natural gas or LPG). LPG installations bring their own checks.
1. Installation checks
Tightness test. Test the installation pipework to the appropriate standard (IGEM/UP/1, UP/1A or UP/1B, depending on size and pressure). Record the result, and the standing and working pressures.
Let-by test. Check the emergency control valve and the interlock solenoid aren't passing gas when closed.
Emergency isolation valve. It must be accessible, operable and clearly labelled for on and off. Staff should know where it is.
Pipework. Look for corrosion, poor support and damage, and check that flexible connections are suitable for catering appliances, restrained, and not kinked, stretched or chafing.
2. Ventilation and interlock
BS 6173 and IGEM/UP/19 require mechanical ventilation in commercial kitchens with gas appliances to be interlocked with the gas supply, so gas can't flow unless the ventilation is running and proven.
- Prove the interlock: switch off the extract fan and confirm the gas shuts off. The proving method may be airflow, pressure differential, fan current, or CO₂ monitoring on suitable installations.
- Check it needs a manual reset after a shutdown, so gas doesn't come back on by itself.
- Record kitchen CO₂ levels with appliances running. A properly ventilated kitchen should stay below 2,800 ppm. IGEM/UP/19 sets a pre-alarm at 2,800 ppm and requires gas to be shut off at 5,000 ppm.
- Record ambient CO as well.
Any interlock override or bypass is unsafe and must be dealt with under the unsafe situations procedure. See Gas interlocks in commercial kitchens.
3. Appliance checks
For each appliance, record make, model, location and appliance type:
- Type A: unflued, products of combustion into the room (for example hobs and some ovens)
- Type B: open flued or under a canopy (most ranges, fryers and griddles in practice)
- Type C: room sealed
Then check and record:
| Check | What you're looking for |
|---|---|
| Operating or burner pressure | Matches the data plate |
| Heat input | Correct for the appliance and gas |
| Flame picture | Stable, correct colour, no lifting, lighting back or yellow tipping |
| Flame supervision (FFD) | Shuts off within the manufacturer's time |
| Ignition | Reliable, no delayed ignition |
| Controls and thermostats | Operate correctly |
| Flue or extraction | Products removed, canopy covers the appliance |
| Stability and restraint | Appliance secure, restraint fitted to mobile appliances |
| Combustion | Flue CO, CO₂ and CO/CO₂ ratio where the appliance allows |
4. Outcome and warning notices
For each appliance and for the installation as a whole, record whether it is safe to use. Where it isn't, follow the Gas Industry Unsafe Situations Procedure and record the classification:
- Immediately Dangerous (ID): disconnect with the responsible person's permission, label it, and leave a warning notice.
- At Risk (AR): turn off with permission, label it, and leave a warning notice.
- Not to Current Standards (NCS): safe to use but doesn't meet current standards. Advise and record it.
The person in charge should sign to say they've been told. More detail is in Gas warning notices: ID, AR and NCS.
5. The record
A good commercial catering gas safety record includes:
- site name and address, date, and the engineer's name and Gas Safe number
- installation results: tightness and let-by tests, pressures, isolation valve, pipework
- ventilation and interlock results, CO₂ and CO readings
- each appliance with its checks and outcome
- defects, warning notices issued, and confirmation the customer was told
- signatures from the engineer and the responsible person
- the date the next inspection is due
Doing it on a phone
CaterTrackr includes a commercial catering gas safety sheet with all of the above: let-by test, isolation valve, kitchen CO₂ and CO, interlock, appliance type, flue readings, and a warning notice outcome with NCS, AR and ID. It also remembers your Gas Safe number, so you don't type it on every job. The customer gets the signed report by email before you're back in the van.
This is a practical overview, not a substitute for the standards. Work to BS 6173, IGEM/UP/19 and the current Gas Industry Unsafe Situations Procedure.